5560 Programmable Delay Device (RTU)
Key Features: 8 Opto-isolated Inputs 8 Relay Outputs Programmable Output Delay Output Boolean of Inputs Wide Range DC Power Input Positive or Negative Ground |
Contact closure alarm conditioning; up to eight optically isolated alarm closure inputs; up to eight relay outputs; outputs related to inputs by user defined logical relationships and time delays; screw-down connections, wall mount, 18 to 72 VDC power supply
Model 5560 Characteristics | |
Inputs and outputs | |
Inputs Outputs |
8 opto-isolated Screw down terminals, 14 to 30 AWG 8 Relays Outputs 1 through 6, Form A, NO Outputs 7 and 8, Form C Relays 1 through 7 have common ground Screw down terminals, 14 to 30 AWG Input Delay: 0 to 65,535 secs (0 to 18 hrs) Boolean operators: and, or, not, xor Output based upon multiple input states related by multiple Boolean operators nested with multiple ( ) operators |
Craft Configuration Port | |
9 pin male D-Sub (DB9M) shielded | RS-232, ASCII, 2400 baud 8/N/1, no parity, no flow control Windows configuration program |
LED Indicators | |
Unit power and status | |
Power | |
Input Power Range Power Consumption Power Connection |
18 to 72 VDC, positive or negative ground 4 Watts Screw down terminals, 14 to 30 AWG |
Environmental | |
Operating Temperature Humidity Range Storage Temperature |
0 to +50° C 5% to 95%, Non-condensing -40 to +70° C |
Physical Characteristics | |
Size Mounting Weight |
6.5” H, 4.5” W, 1.3” D Wall, four #8 holes (two top, two bottom) 1 pounds |